one call
sfs header

Fire Extinguisher

Smith Fire Systems Management has provided fire extinguishers and portable fire extinguisher service for more than 15 years. We strive to provide our customers with quality products and exceptional service. With over 20,000 extinguishers serviced every year, Smith Fire Systems Management's commitment to our customers has never been stronger. This commitment begins with our sales and service of portable fire extinguishers and accessories. With our specialized fire extinguisher shop and staff, customers are offered a unique exchange program. So when you do a search for a fire protection service company, consider our One Call Solution for all your needs. SFSM offers a complete line of service solutions for your needs such as:

  • Testing
  • Inspections
  • Repairs
  • Installation
Fire Extinguishers Monthly Quarterly Semi-annual  Annual Other CODE NFPA 10
  Inspection         4-3.1 Fire extinguishers shall be inspected when initially placed in service and thereafter at approximately 30-day intervals.
  Maintenance         4-4.1 Fire extinguishers shall be subjected to maintenance at intervals of not more than 1 year, at the time of hydrostatic test, or when specifically indicated by an inspection.
  6-Year Maintenance         4-4.3 Every 6 years, stored-pressure fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the applicable maintenance procedures.
  Hydrostatic Test         5.2 Refer to Table 5-2.
  Pressurized Water           5 Years
  Wetting Agent(s)           5 Years
  AFFF Foam           5 Years
  FFFP Foam           5 Years
  Carbon Dioxide (CO2)           5 Years
  Dry Chemical(s)           12 Years
  Halogenated Agent(s)           12 Years
  Hose Conductivity Testing         4-4.1.2 A conductivity test shall be conducted annually on all carbon dioxide hose assemblies.
               

For 24 Hour Emergency Service call 1-866-697-3987